CHAPTER 5
Mounting and Clearance Requirements
Rack Requirements for EX2200 Switches on page 39
Cabinet Requirements for EX2200 Switches on page 40
Requirements for Mounting an EX2200 Switch on a Desktop or Wall on page 42
Clearance Requirements for Airflow and Hardware Maintenance for EX2200
Switches on page 42
Rack Requirements for EX2200 Switches
You can mount the switch on two-post racks or four-post racks.
Rack requirements consist of:
Rack type
Mounting bracket hole spacing
Rack size and strength
Rack connection to the building structure
Table 18 on page 39 provides the rack requirements and specifications for the switch.
Table 18: Rack Requirements and Specifications for the Switch
GuidelinesRack Requirement
Use a two-post rack or a four-post rack. You can mount the switch on any two-post or four-post
rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in./4.45 cm) increments and
that meets the size and strength requirements to support the weight.
A U is the standard rackunit defined in Cabinets, Racks, Panels, and Associated Equipment (document
number EIA-310–D) published by the Electronics Industry Association (http://www.eia.org).
The rack must meet the strength requirements to support the weight of the chassis.
Rack type
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the switch can
be mounted in any rack that provides holes spaced at that distance.
Mounting bracket hole
spacing
39Copyright © 2010, Juniper Networks, Inc.